| Model NO. | ZW7-40.5 | Arc-extinguishing Medium | Vacuum |
| Installation | Open Frame |
Structure | ACB |
| Poles Number | 3 | Type | Circuit Breaker |
| Function | Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection) | Certification | ISO9001-2000, |
| Rated Voltage | 33kv~35kv | Current Rating | 630A~2000A |
| Rated Frequency | 50Hz-60Hz | Weight | 700Kg |
| Transport Package | Export Standard Wooden Case | Trademark | CHNGS |
| Origin | China |
Rated Short-Circuit Interrupting Current | 20 25 31.5 |
| Specification | 3100*2700*1400mm |
| serial number | project | unit | parameter | ||
| 1 | Rated voltage | KV | 40.5 | ||
| 2 | Rated insulation level | 1min power frequency withstand voltage | Dry test | KV | 95 |
| Wet test | KV | 80 | |||
| Lightning impulse withstand voltage (peak) | KV | 185 | |||
| 3 | Current rating | A | 1250,1600,2000 | ||
| 4 | Rated short-circuit interrupting current | KA | 20,25,31.5 | ||
| 5 | Rated sequence of operations | min-0.3s-combine-180s-combine | |||
| 6 | Rated number of short-circuit current interruptions | times | 12 | ||
| 7 | Rated short-circuit closing current (peak) | KA | 50,63,80 | ||
| 8 | Rated peak withstand current | KA | |||
| 9 | Rated short-time withstand current | KA | 20,25,31.5 | ||
| 10 | Rated short-circuit duration | S | 4 | ||
| 11 | Contact opening distance | mm | 22±2 | ||
| 12 | Contact overtravel | mm | 4±1 | ||
| 13 | Average opening speed | m/s | 1.5±0.2 | ||
| 14 | Average closing speed | m/s | 0.7±0.2 | ||
| 15 | Contact closing bounce time | mS | ≤2 | ||
| 16 | Three-phase (split) gate synchronous time difference | mS | ≤2 | ||
| 17 | Closing time | ms | ≤150 | ||
| 1Q | Opening time | mS | ≤60 | ||
| 19 | Mechanical life | times | 10000 | ||
| 20 | Rated operating voltage, auxiliary circuit rated voltage | V | DC110/220,AC110/220 | ||
| 21 | Current resistance per phase loop (without transformer) | μΩ | ≤100 | ||
| 22 | weight | kg | 700 | ||