LW36-126/3150-40 HV SF6 Circuit Breaker

Description

Product Details

1.1 The main purpose and scope of application

LW36-126/3150-40 high voltage SF6 circuit breaker (equipped with CTB type spring operating mechanism) is an outdoor AC three-phase 50Hz high-voltage power transmission and transformation equipment, used to open and close rated current, fault current or change the line to realize the protection, control and operation of the power transmission and transformation system, and can perform three-phase opening fast and automatic reclosing operation.

The circuit breaker has the latest design principles, simple structure, small size, less consumables; Low energy operation, high reliability, easy installation and low noise.

 

1.2 Environmental conditions

Environment temperature: -30℃~+40℃

Wind pressure is not more than 700Pa

Altitude not greater than 2000m

Earthquake intensity is not more than 9 degrees

The degree of air pollution is not greater than Grade IV

 

1.3 Rated parameters

1.3.1 The rated parameters of the circuit breaker and operating mechanism are shown in Table 1

No.

Name

Unit

Value

1

Rated voltage

kV

126

2

Rated insulation level

kV

Table 2

3

Rated frequency

Hz

50

4

Rated current

A

3150

5

Rated short circuit breaking current

kA

40

6

Rated peak withstand current

kA

100

7

Rated short circuit duration

s

4

8

Rated short circuit closing current(peak)

kA

100

9

Short-line fault breaking current

kA

L90:36, L75:30

10

Rated line charging breaking current

A

31.5

11

Rated out-of-phase breaking current

kA

10

12

Out-of-phase ground fault breaking current

kA

34.8

13

Cumulative breaking times under rated short-circuit breaking current

times

20

14

First pole factor

 

1.5(cover 1.3)

15

SF6 gas pressure (20℃)

MPa

Table 3

16

Main mechanical characteristics

 

Table 4

17

Rated operating sequence

 

O-0.3s-CO-180s-CO

18

Main circuit resistance

μΩ

≤45

19

Terminal static load

Horizontal and vertical Ftha

N

1250

Horizontal Fthb

N

750

Vertical direction Ftv

N

1000

Force generated by wind pressure Fwh

N

500

20

Mechanical life

times

6000

21

SF6 gas annual leakage rate

 

≤1%

22

SF6 gas moisture content (V/V)

ppm

≤150

23

Rated voltage of control circuit and auxiliary circuit power supply

V

Table 5

24

Total weight of circuit breaker (including mechanism)

kg

1700

25

Total weight of SF6 gas

kg

6

26

Outline dimensions of the circuit breaker

mm

4000*560*4942

 

Table 2 Rated insulation level (kV)

No.

Name

Main value

1

Power frequency withstand voltage/min (effective value, dry test, wet test)

Between gaps

265/300

Between phases or phase to ground

230/260

2

Lightning impulse withstand voltage (Full wave 1.2/50Μs) (peak value)

Between gaps

630/712

Between phases or phase to ground

550/622

3

When SF6 gas has zero gauge pressure, 5min power frequency withstand voltage (effective value)

Between gaps

95

Phase to ground

95

Note: The parameter in NO. 1 and NO. 2 is the insulation level at an altitude of 2000m.

 

Table 3 SF6 gas pressure (20℃)

NO.

Name

SF6 gas parameters

1

Rated working pressure PN

0.50±0.015

2

Air supply alarm pressure P1A

0.45±0.015

3

Circuit breaker locking pressure P2A

0.40±0.015

4

Pressure difference between P1A and P2A

0.048±0.052

5

Replenish gas alarm and relieve pressure P1B

0.48±0.015

6

Circuit breaker locking relieve pressure P2B

0.43±0.015

7

Inflation pressure during product packaging and transportation P3

0.025

 

Table 4 Main mechanical characteristics

NO.

Name

Unit

Value

1

Moving contact stroke

mm

148±4

2

Contact stroke of moving contact

mm

25±2

3

Contact clearance

mm

120±2

4

Opening time

ms

28±5

5

Closing time

ms

≤110

6

O-C time

ms

Factory value ≤300, operating value≥300

7

C-O time

ms

Factory value ≤60, operating value≥60

8

Opening simultaneity

ms

≤3

9

Closing simultaneity

ms

≤5

10

Breaking time

ms

≤60

11

Opening speed

M/s

4.8±0.5

12

Closing speed

M/s

2.8±0.5

 

Table 5 Rated voltage of control circuit and auxiliary circuit power supply

NO.

Name

Unit

Value

1

Control and signal circuit voltage

V

DC220/DC110

2

Motor voltage/power frequency

V/W

DC/AC 220/650

3

Moisture heating circuit voltage

V

AC220

4

Rated current of closing coil

A

2/3.67

5

Rated current of opening coil

A

2.3/3.67


Appearance And installation Dimensions